一、LYDCS-2000B多功能級差配合測試儀概述  

目前變電(dian)(dian)(dian)(dian)(dian)站(zhan)的(de)直(zhi)流(liu)(liu)(liu)(liu)饋(kui)電(dian)(dian)(dian)(dian)(dian)網絡(luo)多(duo)采(cai)用樹狀(zhuang)結構(gou),從蓄電(dian)(dian)(dian)(dian)(dian)池到站(zhan)內用電(dian)(dian)(dian)(dian)(dian)設(she)備,一般(ban)經(jing)過(guo)三級(ji)配(pei)電(dian)(dian)(dian)(dian)(dian),每級(ji)配(pei)電(dian)(dian)(dian)(dian)(dian)大多(duo)采(cai)用直(zhi)流(liu)(liu)(liu)(liu)斷路器(qi)(qi)(qi)作為保(bao)(bao)(bao)護(hu)電(dian)(dian)(dian)(dian)(dian)器(qi)(qi)(qi)。由于上下(xia)級(ji)直(zhi)流(liu)(liu)(liu)(liu)斷路器(qi)(qi)(qi)保(bao)(bao)(bao)護(hu)動(dong)作特性(xing)不(bu)匹配(pei),在直(zhi)流(liu)(liu)(liu)(liu)系統(tong)運行過(guo)程(cheng)中,當下(xia)級(ji)用電(dian)(dian)(dian)(dian)(dian)設(she)備出現(xian)短路故(gu)障時,經(jing)常引起上一個直(zhi)流(liu)(liu)(liu)(liu)斷路器(qi)(qi)(qi)的(de)越級(ji)跳(tiao)閘(zha),從而引起其它饋(kui)電(dian)(dian)(dian)(dian)(dian)線路的(de)斷電(dian)(dian)(dian)(dian)(dian)事故(gu),進而引起變電(dian)(dian)(dian)(dian)(dian)站(zhan)一次設(she)備如高(gao)壓(ya)開關、變壓(ya)器(qi)(qi)(qi)、電(dian)(dian)(dian)(dian)(dian)容器(qi)(qi)(qi)等的(de)事故(gu)。為防止因直(zhi)流(liu)(liu)(liu)(liu)斷路器(qi)(qi)(qi)及其它直(zhi)流(liu)(liu)(liu)(liu)保(bao)(bao)(bao)護(hu)電(dian)(dian)(dian)(dian)(dian)器(qi)(qi)(qi)動(dong)作特性(xing)不(bu)匹配(pei)帶來(lai)的(de)隱患,國家(jia)電(dian)(dian)(dian)(dian)(dian)網公司對于新裝和運行中的(de)直(zhi)流(liu)(liu)(liu)(liu)保(bao)(bao)(bao)護(hu)電(dian)(dian)(dian)(dian)(dian)器(qi)(qi)(qi),規定了(le)必須進行安秒特性(xing)測試,保(bao)(bao)(bao)證性(xing)能(neng)與(yu)設(she)計相符,以確保(bao)(bao)(bao)直(zhi)流(liu)(liu)(liu)(liu)回路級(ji)差配(pei)合的(de)正確性(xing)。2005年發布的《直(zhi)流電源系統運行規范(fan)》第十(shi)二條第八款規定直(zhi)流(liu)熔斷(duan)器和(he)空氣斷(duan)路(lu)器應(ying)采用質量合(he)格的產品,其(qi)熔斷(duan)體或定值應(ying)按有關規(gui)定分(fen)級配置和(he)整定,并定期進(jin)行(xing)核對,防止(zhi)因其(qi)不正確(que)動作而(er)擴(kuo)大(da)事(shi)(shi)故”;《直(zhi)流(liu)電源系統(tong)(tong)技(ji)術監督規(gui)定》第二十(shi)七條中規(gui)定:“…自(zi)動空氣斷(duan)路(lu)器使用前應(ying)進(jin)行(xing)特性和(he)動作電流(liu)抽查。…”;《預防直(zhi)流(liu)電源系統(tong)(tong)事(shi)(shi)故措施》第十(shi)一條中規(gui)定:“…使用前宜進(jin)行安秒特性和動作電流(liu)抽檢(jian)…”

直流保護電(dian)(dian)器(qi)的安秒特性一般(ban)在實(shi)驗室(shi)或(huo)檢測(ce)站進行(xing)測(ce)試(shi),設(she)備占地面積(ji)大(da),需要配置專(zhuan)門(men)的充(chong)電(dian)(dian)裝置和大(da)電(dian)(dian)流負載(zai)箱,操作復雜;部分運行(xing)單位利用變電(dian)(dian)站蓄電(dian)(dian)池組對(dui)直流保護電(dian)(dian)器(qi)的級差配合進行(xing)試(shi)驗,但無法(fa)準確(que)測(ce)試(shi)其電(dian)(dian)流-動作(zuo)時間特性。因(yin)(yin)而造成直(zhi)流系統投運后,現場檢修維護人(ren)員因(yin)(yin)不具備相應的(de)測試手段和工具,無法檢驗直(zhi)流保護電器的(de)安秒特性是否滿足要求。

根據直流(liu)(liu)保(bao)(bao)護電(dian)器(qi)(qi)安秒(miao)特性(xing)測試(shi)的(de)現實狀(zhuang)況,本公司(si)推出了(le)一(yi)種適合(he)(he)變電(dian)站(zhan)現場使用、便于攜帶、自動(dong)化程度高的(de)直流(liu)(liu)斷路(lu)器(qi)(qi)安秒(miao)特性(xing)測試(shi)及(ji)級差配(pei)合(he)(he)綜(zong)合(he)(he)系(xi)統(tong),可以為運行維護部(bu)門(men)提供直流(liu)(liu)保(bao)(bao)護電(dian)器(qi)(qi)動(dong)作特性(xing)的(de)測試(shi)手段,對直流(liu)(liu)保(bao)(bao)護電(dian)器(qi)(qi)的(de)動(dong)作特性(xing)以及(ji)級差配(pei)合(he)(he)進行校驗,以便提高直流(liu)(liu)系(xi)統(tong)運行的(de)可靠性(xing),保(bao)(bao)證(zheng)電(dian)網(wang)的(de)可靠運行。

二、LYDCS-2000B多功能級差配合測試儀?產品特點

儀器既(ji)可以單獨使(shi)用,也可以與PC機聯機使(shi)用(yong)。

儀器提供直流大(da)電流源使用簡便(bian),無(wu)需提供蓄電池等直流電源。

320×240液(ye)晶顯示器(qi)、高速熱敏打印機,人機對話全鍵盤操作方式,智能化工作全過程。

采(cai)用電力電子控制技(ji)術產生直流(liu)大(da)電流(liu)輸出,輸出電流(liu)響應速(su)度快、精度高、連續(xu)可(ke)調。

多個(ge)高(gao)精度傳(chuan)感器自動(dong)切(qie)換電流量程和(he)高(gao)性(xing)能14AD采集(ji)芯(xin)片(pian)。

具有掉電存儲功能,可以存1000組試驗數據。

自(zi)動保存(cun)設置數據,掉電后開機后顯示上一(yi)次的(de)設置數據。

具有安(an)秒動作(zuo)試(shi)驗(yan)方式、通流不動作(zuo)試(shi)驗(yan)、脫(tuo)扣測(ce)試(shi)試(shi)驗(yan)、差級配合試(shi)驗(yan)、內阻測(ce)試(shi)試(shi)驗(yan)五大試(shi)驗(yan)。*兼(jian)容全點(dian)測(ce)試(shi)和(he)抽(chou)點(dian)測(ce)試(shi)。

儀器提供RS232通(tong)信接口,電腦(nao)*可以控制儀器并導出試(shi)驗數(shu)據(ju)。

聯機使用方(fang)式時,可以操作控制儀(yi)器、導(dao)入試(shi)驗數據(ju)、存儲試(shi)驗數據(ju)、生(sheng)成數據(ju)報表、生(sheng)成數據(ju)曲線、生(sheng)成EXCEL報表等(deng)。

儀器帶(dai)有過熱、過流(liu)、過壓(ya)保護(hu)保護(hu)功能。

儀器抗(kang)干擾能(neng)力強,電磁兼容性(xing)能(neng)強。

三(san)、技術指標(biao)

電源輸入:220V±10%,頻率:50Hz±0.5 Hz

測試電流范(fan)圍:0500A

測試(shi)電壓范圍:0-1.0V

測試電流紋波系(xi)數(shu):小于5%

輸(shu)出電流的穩定性:≤0.5%

時(shi)間記(ji)錄:0-9999S;時間分辨率:0.1mS

環境溫(wen)度(du):-2050

外形尺寸:470mm()×320mm(寬)×460mm(高);

重量:20kg

四、使用方(fang)法

1. 按試驗要(yao)求正確接線

2. 控制箱的(de)面(mian)板結構圖

3. 儀器本機軟件使(shi)用(yong)

1)開機界面

開(kai)機(ji)處于“歡迎界面”,如圖3

根據鍵盤的(de)示圖4,按上↑、下(xia)↓、左←,右→可以切換(huan)菜(cai)單項。

2)設置試驗參數

主界面(mian)選(xuan)中“試驗(yan)參(can)數(shu)設置(zhi)”后,按(an)確(que)定(ding)可以進入設置(zhi)界面(mian),如(ru)圖5:

按左←,右→時切換光(guang)(guang)標(biao)(biao)移動位置(zhi),按上(shang)↑、下↓時更改光(guang)(guang)標(biao)(biao)位置(zhi)數(shu)據的(de)值(zhi)。光(guang)(guang)標(biao)(biao)位置(zhi)和設置(zhi)的(de)數(shu)值(zhi)全部可以自動循環,前且(qie)在(zai)使用時有默認的(de)標(biao)(biao)準值(zhi)。如果所有的(de)參數(shu)都設置(zhi)完成,按取消退(tui)出設置(zhi)回到(dao)主界面(mian)開始狀態。

額(e)定(ding)(ding)電(dian)流(liu)(liu):直流(liu)(liu)斷路器的額(e)定(ding)(ding)電(dian)流(liu)(liu)。

電流倍(bei)數:相對額(e)定電流的倍(bei)數。

試驗時(shi)間:電流輸出的長時(shi)間。

準備時間:開始試驗前的等待時間。

起始倍數:脫扣測試(shi)試(shi)驗(yan)逐級過程中的開(kai)始的電流(liu)倍數。

步(bu)(bu)進(jin)倍數:脫扣測(ce)試(shi)試(shi)驗逐級(ji)過程中的(de)步(bu)(bu)進(jin)電流(liu)倍數。

大倍數:脫扣(kou)測試試驗逐級過程(cheng)中的大的電流倍數。

準備時間應根據規(gui)程(cheng)來設置,不宜過短。直流斷路器在連續(xu)試驗中,應保證直流斷路器冷卻(que)。

輸出(chu)電流 = 額定電(dian)流(liu)X電(dian)流倍數不能超過(guo)本機大電(dian)流,輸出電(dian)流小于200A,試驗時間不超過9999S;輸(shu)出電流大(da)于200A,試驗時間不超(chao)過(guo)300S

3)安秒動作試驗

主界面(mian)選中“安秒動作(zuo)試驗”后,按確(que)定可以(yi)進入設置界面(mian),如(ru)圖6:

安秒動作試驗用來檢(jian)測

直流(liu)斷路器開斷(電流(liu)倍數(shu)—時(shi)間)的特(te)性試驗(yan)。根據規程,電流(liu)倍數(shu)從2~N(不(bu)(bu)同直流斷路器不(bu)(bu)等)進行試驗,每個電流倍數下要(yao)(yao)求進行三(san)次試驗,獲得的三(san)個動作(zuo)時間(jian),動作(zuo)時間(jian)的平均值連線(xian)要(yao)(yao)落(luo)在規程中的閉絡線(xian)(可以用PC機來做些曲(qu)線)。此試(shi)驗計時(shi)相(xiang)對更(geng)加(jia)靈敏。

界(jie)面(mian)劃(hua)分(fen)試驗(yan)(yan)結果顯示(shi)區(qu)(qu),基(ji)本參數顯示(shi)區(qu)(qu),試驗(yan)(yan)提示(shi)區(qu)(qu),試驗(yan)(yan)操作區(qu)(qu)。

結果顯示區:以表格方(fang)式顯示試驗(yan)結果,標題(ti)欄為額(e)定電流、電流倍數、試驗(yan)時(shi)間、開始試驗(yan)時(shi)刻。中(zhong)間為試驗(yan)記(ji)錄,可(ke)以存200條。底下為記(ji)錄(lu)顯示(shi)匯總,有試(shi)驗(yan)記(ji)錄(lu)條數、6條每頁(ye),光標所在哪一頁(ye),光標選(xuan)擇第幾條。按上↑、下↓鍵(jian)可以移動選(xuan)擇,選(xuan)中(zhong)記錄加粗顯示(shi)。

試驗操作區:按左(zuo)←,右→鍵(jian)選擇清空、刪除、試驗。

“清空(kong)”——按確定將(jiang)清理本試驗(yan)所有試驗(yan)數據;

“刪(shan)除”——按確定(ding)將刪(shan)除光(guang)標選擇的(de)試驗記錄;

“試(shi)(shi)驗(yan)”——按確定將(jiang)進行試(shi)(shi)驗(yan);

按(an)面(mian)板打(da)印可(ke)以打(da)印選(xuan)擇的試驗記錄。

 

試驗前檢(jian)查:

斷路(lu)器(qi)檢查——直流斷路(lu)器(qi)是(shi)否(fou)斷開其它的電氣連接(jie),是(shi)否(fou)已經合閘(zha)。

連接(jie)檢查——本裝置輸出(chu)的是恒流直流電流,務必把每一接(jie)觸(chu)點接(jie)牢扭(niu)緊。

試(shi)驗過程(cheng):

系統先計時(shi)(shi)“準(zhun)(zhun)備時(shi)(shi)間(jian)”,準(zhun)(zhun)備時(shi)(shi)間(jian)計時(shi)(shi)結束后開始輸出電流。

電流輸出為開始時(shi)刻,過(guo)程中自動捕(bu)捉直(zhi)流斷(duan)路器的(de)跳閘狀態為結束時(shi)刻,兩者時(shi)間(jian)差為動作時(shi)間(jian)。

電流輸出(chu)(chu)過(guo)程中按取(qu)消鍵,可以退出(chu)(chu)試驗;根據(ju)設置的試驗時間(jian),計時到了也退出(chu)(chu)試驗,通流試驗時間(jian)應大于(yu)動(dong)作(zuo)(zuo)時間(jian),動(dong)作(zuo)(zuo)時間(jian)記錄中有(you)“>”符號,說(shuo)明在(zai)通(tong)流(liu)時(shi)間(jian)內未動作(zuo)。

電流輸出過程中,3秒內測試電流(liu)沒有升起(qi)來(lai),系統(tong)會自(zi)動提示斷路(lu)(lu)器開路(lu)(lu),請確保直流(liu)斷路(lu)(lu)器合閘。

試(shi)驗(yan)(yan)結束后,系統自(zi)動斷開輸出(chu)電流,并(bing)存(cun)儲試(shi)驗(yan)(yan)數據,在(zai)試(shi)驗(yan)(yan)結果區可以看到一(yi)條(tiao)新的試(shi)驗(yan)(yan)記錄。

5)通流不動(dong)作試驗

通(tong)(tong)流(liu)(liu)不動作試驗(yan)(yan)用來檢測直流(liu)(liu)斷(duan)路(lu)器(qi)在通(tong)(tong)過額(e)定(ding)(ding)電(dian)流(liu)(liu)左右(you)電(dian)流(liu)(liu)的(de)穩(wen)定(ding)(ding)性能的(de)特(te)性試驗(yan)(yan)。規(gui)(gui)程(cheng)規(gui)(gui)定(ding)(ding)1.13倍一小時內(nei)不動作,1.45倍(bei)一小(xiao)時(shi)內動作。

試驗(yan)方法類似安秒(miao)動作試驗(yan)。

6)脫扣測(ce)試(shi)試(shi)驗(yan)

脫(tuo)(tuo)扣測試試驗用來檢測直流斷路器的(de)脫(tuo)(tuo)扣電流倍數和(he)動作時間。此試(shi)驗(yan)是(shi)一(yi)個逐級(ji)升流試(shi)驗(yan)過程。

準備時間,輸出電(dian)流=額定電(dian)流X起始倍數。試(shi)驗(yan)時間計時結束。

準備(bei)時間,輸出(chu)電流=額定電流X(起始倍數+步(bu)進(jin)倍數)。試驗時間計時結束。

準(zhun)備(bei)時(shi)間,輸出電流=額定電流X(起(qi)始倍數+2X步進倍數(shu))。試驗時間計時結(jie)束。

… …

N次,準(zhun)備時間,輸出電流=額(e)定電流X(起始倍數+N-1X步進(jin)倍(bei)數(shu))。試(shi)驗時間計時結束。

直至倍數大于大電流倍數,逐(zhu)(zhu)級升(sheng)流試(shi)驗結束(shu)。在(zai)逐(zhu)(zhu)級升(sheng)流過程中,若直流斷路器動作,逐(zhu)(zhu)級升(sheng)流試(shi)驗結束(shu)。每次試(shi)驗數據將自動保(bao)存起來(lai)。

7)差級配合(he)試驗

差級配合試驗用來檢測多級直(zhi)流斷(duan)路器的(de)配合情況。模擬短路時(shi),應小一個直(zhi)流斷(duan)路器動作,回路斷(duan)開后(hou)上級直(zhi)流斷(duan)路器不(bu)動作。接線方法(fa)如下,圖7

上(shang)圖(tu)按典型(xing)的(de)三級(ji)直(zhi)流斷路器(qi)(qi)來接(jie)線,多級(ji)類似(si)。試驗方法類似(si)安秒動作試驗。特(te)別說(shuo)明,小型(xing)直(zhi)流斷路器(qi)(qi)的(de)內阻過大,儀器(qi)(qi)輸出(chu)功(gong)率限制,建議級(ji)數減少來測試。

8)內阻測試試驗

內(nei)阻(zu)測試試驗(yan)用來測試直流(liu)斷(duan)路器的內(nei)阻(zu)。接線方法如下,圖8

此試(shi)(shi)驗,要求使(shi)用電壓信號線,請按(an)正負接(jie)入。試(shi)(shi)驗自動(dong)按(an)的(de)電流倍數來測試(shi)(shi)斷路(lu)器的(de)內阻(zu)。試(shi)(shi)驗方法類(lei)似安秒(miao)動(dong)作試(shi)(shi)驗。

9)功能選(xuan)擇(ze)

按鍵(jian)盤上的“功能”就進入(ru)功能界面,如圖9:

進入功(gong)能界面(mian)后,可以選擇(ze) “系(xi)統日歷時鐘(zhong)調整”、“清理全部歷史數(shu)”、“試(shi)驗(yan)操作注意事(shi)項(xiang)”等(deng)界面(mian)。

系統日歷時鐘調整:設置時鐘的時間(jian),為試(shi)驗數據(ju)提供時間(jian)依據(ju)。

清理全部(bu)歷史數(shu):清理儀器存(cun)儲(chu)器中所(suo)有的試驗數(shu)據(ju)。

試(shi)驗操(cao)作注意事項:為用(yong)戶(hu)提(ti)供一(yi)些操(cao)作規范和注意事項。

五、PC機聯機使用方法(fa)

1. 儀器與PC機聯機

儀器與PC機之間(jian)通(tong)過RS232線相連。如果PC機不帶串口,可選(xuan)配USB-RS232連接線(xian)。

PC機聯機使(shi)用比單獨儀器(qi)操(cao)作更方便(bian),操(cao)作步驟大致(zhi)分為:

設(she)置參數——開始試驗——導入(ru)數據——保存文件(jian)——生成報表。

2. PC機軟件(jian)配置

將光盤(pan)打(da)開后,可以(yi)看到一個“上(shang)位(wei)機”文件夾(jia),將其拷貝到PC機的根(gen)目(mu)錄中,打(da)開(kai)此文件(jian)夾(jia),如(ru)圖11

其中“ZUC.exe”是本系統的主執行文件(jian),“DATA”文件夾為試(shi)驗數(shu)據目(mu)錄,試(shi)驗數(shu)據以時間(jian)為文件名存儲。導出(chu)的EXCEL格式的(de)數據也放在此(ci)文件夾。雙擊“ZUC.exe”執行文件,打開主界面,如(ru)圖12

3.軟件使用

1)打開文件:打開以前的數據文件,可以添加試驗記(ji)錄(lu),或進行打印。

2)保存文件(jian):保存試驗(yan)數據為數據文件(jian),可以在PC機存儲(chu)。

3)導(dao)出EXCEL:可(ke)以導出當前的數(shu)據為(wei)EXCEL文件,文件內容如圖(tu)13

4)打印預覽:可以查看當前試驗數據的報表,如圖14

5)試(shi)驗界面:進行(xing)與儀器聯機(ji),進行(xing)試(shi)驗操(cao)作,并導入(ru)試(shi)驗數(shu)據。

6)退(tui)出系(xi)統:可以(yi)退(tui)出本(ben)系(xi)統軟件。

7)打開“幫(bang)助(zhu)”菜單,選擇“幫(bang)助(zhu)文檔”可(ke)以打開幫(bang)助(zhu)文檔的電子版。

4. 試驗方(fang)法

打開“試驗界面”,如圖(tu)15

按“斷(duan)(duan)路(lu)(lu)器信息”欄(lan)目,可以輸入(ru)直流斷(duan)(duan)路(lu)(lu)器的相關信息,方便生成(cheng)報(bao)表。可以輸入(ru)試(shi)驗(yan)單位、試(shi)驗(yan)人(ren)員、廠站(zhan)名(ming)、斷(duan)(duan)路(lu)(lu)器編號、斷(duan)(duan)路(lu)(lu)器型號、斷(duan)(duan)路(lu)(lu)器品(pin)牌(pai)、斷(duan)(duan)路(lu)(lu)器特(te)性。

按“安秒特性試驗(yan)(yan)結(jie)果”欄目(mu),將顯示本直流斷路器的安秒動作試驗(yan)(yan)數(shu)(shu)據(ju),左邊是(shi)數(shu)(shu)據(ju)形式,右邊為數(shu)(shu)據(ju)曲線。

按“通流(liu)不動作(zuo)試驗(yan)結果”欄目,將顯示本直流(liu)斷路器的通流(liu)不動作(zuo)試驗(yan)數據。

按(an)“脫(tuo)扣測試(shi)試(shi)驗結果”欄目,將顯示本直流斷路器的(de)脫(tuo)扣測試(shi)試(shi)驗數據。

按“差級配(pei)合試驗結果”欄目,將顯示(shi)本直流斷路器的差級配(pei)合試驗數據。

按(an)“內阻測試試驗(yan)結果(guo)”欄目,將顯(xian)示本(ben)直流斷路器的內阻測試試驗(yan)數(shu)據。

按“試(shi)驗(yan)”,將彈出試(shi)驗(yan)命(ming)令界面(mian),如圖21

A、進入此界面前,設置(zhi)額定電(dian)(dian)流(liu)(liu)(liu)和開關類(lei)型。一(yi)個(ge)試驗數據(ju)文件只(zhi)包含一(yi)個(ge)直流(liu)(liu)(liu)斷路(lu)(lu)器(qi)的(de)試驗數據(ju),因此額定電(dian)(dian)流(liu)(liu)(liu)是不(bu)變(bian)的(de),試驗首(shou)先設置(zhi)額定電(dian)(dian)流(liu)(liu)(liu)。額定電(dian)(dian)流(liu)(liu)(liu)改變(bian),將(jiang)認為已經(jing)更換(huan)了新的(de)直流(liu)(liu)(liu)斷路(lu)(lu)器(qi),系統將(jiang)會清空(kong)以(yi)前的(de)試驗記錄。根據(ju)直流(liu)(liu)(liu)斷路(lu)(lu)器(qi)類(lei)型不(bu)同,請(qing)選擇B型或C型的曲線包(bao)羅(luo)線。

B、試驗前,請按儀(yi)器(qi)單獨使用時一樣,必須進行(xing)相關檢查。閉(bi)合直流斷路器(qi),連接好串口線。

設置好(hao)此界面中的配置數據,選擇串口(kou)號,按“連接儀器(qi)測試”按鈕測試PC機(ji)和儀(yi)器是否聯通。

C、連接儀器測試(shi)成功后(hou),請設置試(shi)驗(yan)參數數據。試(shi)驗(yan)類型、電(dian)(dian)流(liu)倍數、試(shi)驗(yan)時間、準(zhun)備時間、起始電(dian)(dian)流(liu)、步(bu)進電(dian)(dian)流(liu)、大電(dian)(dian)流(liu)。

D、按(an)(an)(an)“開始試(shi)驗”按(an)(an)(an)鈕,儀器(qi)將進行試(shi)驗并輸出電流,直到試(shi)驗結束,如果過程中要停止試(shi)驗,可以按(an)(an)(an)“中斷試(shi)驗”按(an)(an)(an)鈕。

E、試驗結束(shu)后,請按“上傳(chuan)本試驗近(jin)數據”按鈕,將會(hui)把剛才的試驗數據傳(chuan)上來,并(bing)在對應的試驗結果界面(mian)中(zhong)顯示(shi)出來。

做安秒動(dong)作(zuo)(zuo)試驗時,請(qing)在(zai)同一倍數額定電流下重(zhong)復做三(san)次試驗,軟件會(hui)自動(dong)求(qiu)動(dong)作(zuo)(zuo)時間的平均值顯示在(zai)曲線(xian)中。

做(zuo)脫扣測試(shi)試(shi)驗時(shi),儀器將做(zuo)逐級試(shi)驗,整個過程完成(cheng)后,可以(yi)一次(ci)性導入全部試(shi)驗數據。

做級差配合試(shi)驗時,導入數據要求人為(wei)設置每(mei)級斷路器是否動作。

“清(qing)理(li)儀器(qi)(qi)(qi)所有(you)數(shu)據”、“清(qing)理(li)全(quan)部顯(xian)示數(shu)據”、“上(shang)傳(chuan)本(ben)試驗(yan)(yan)所有(you)數(shu)據”不經常使用。“清(qing)理(li)儀器(qi)(qi)(qi)所有(you)數(shu)據”為(wei)(wei)清(qing)理(li)儀器(qi)(qi)(qi)存(cun)儲器(qi)(qi)(qi)中(zhong)(zhong)的(de)試驗(yan)(yan)數(shu)據。“清(qing)理(li)全(quan)部顯(xian)示數(shu)據”為(wei)(wei)清(qing)理(li)試驗(yan)(yan)界面中(zhong)(zhong)的(de)所有(you)數(shu)據。“上(shang)傳(chuan)本(ben)試驗(yan)(yan)所有(you)數(shu)據”為(wei)(wei)將儀器(qi)(qi)(qi)中(zhong)(zhong)本(ben)試驗(yan)(yan)所有(you)的(de)試驗(yan)(yan)數(shu)據上(shang)傳(chuan)上(shang)來,存(cun)放到試驗(yan)(yan)界面中(zhong)(zhong)。

六、注意事項

儀器(qi)應放置于(yu)干燥、通風,無腐蝕(shi)性氣體的室內。

請不要私自拆卸、分解或改造儀器,否則有觸電的(de)危險(xian)。

請不要私自(zi)維修儀器(qi)(qi)或自(zi)主改造、加工儀器(qi)(qi),否則儀器(qi)(qi)不在質保之(zhi)列。

為(wei)發揮本產品的(de)性(xing)能(neng),在使(shi)用(yong)本公司產品前請仔細閱讀(du)使(shi)用(yong)說明(ming)書。

七(qi)、運輸(shu)、貯(zhu)存

■運輸(shu)

設備需要(yao)運(yun)輸時,建議使用本公司儀器包裝木箱和減(jian)震物品,以免在(zai)運(yun)輸途中造成(cheng)不必要(yao)的(de)損壞,給您造成(cheng)不必要(yao)的(de)損失。

設備在運輸途中不使用木箱(xiang)時(shi),不允許堆(dui)碼排放。使用本公司儀器包裝箱(xiang)時(shi)允許堆(dui)碼層數為(wei)二層。

運輸設備途中,儀器面板應朝上。

■貯存

設(she)備應放置在(zai)干燥無塵、通風無腐蝕性氣(qi)體(ti)的室內。在(zai)沒有(you)木箱包(bao)裝的情況(kuang)下(xia),不(bu)允許堆碼排放。

設備貯存時,面板(ban)應(ying)朝上。并(bing)在(zai)設備的(de)底部墊防潮物品,防止(zhi)設備受潮。

留言框

  • 產品:

  • 您的單位:

  • 您的姓名:

  • 聯系電話:

  • 常用郵箱:

  • 省份:

  • 詳細地址:

  • 補充說明:

  • 驗證碼:

    請(qing)輸入(ru)計算結果(填寫阿拉伯(bo)數字),如:三加四=7